62
See the table Universal Output Functionality and Restrictions for
relay terminal connections for other Output Algorithm Types.
Figure 3-11: Position Proportional or Three Position Step Control
Connections, model DC2800-EE or DC2900-EE
Item Description
1 Alarm #2 is not available with this configuration.
2 DC2800-EE or DC2900-EE Electromechanical Relays are rated at 5 Amps at
120 Vac or 240 Vac or 24 Vdc.
Users should size fuses accordingly. Use Fast Blow fuses only.
3 See Input 2 Wiring Diagram for Slidewire Connections.
Figure 3-12: Position Proportional or Three Position Step Control
Connections, model DC2800-R_ or DC2900-R_
Item Description
1 Alarm #2 is not available with this configuration.
2 DC2800-R_ or DC2900-R_ Dual Electromechanical Relays are rated at 2 Amps
at 120 Vac or 240 Vac or 30 Vdc.
Chapter 3 - Installation