NOTE: Restricted Access refers to an inaccessible location that is normally
inaccessible by the general public by means of any administrative or
engineering control measure, but is accessible to authorized personnel who
might not have laser safety training.
Table 5: Environmental Site Requirements
RequirementsSite Criteria
BTI7800 equipment must be installed in a
Restricted Access Location in the Central Office
(CO) of Network Telecommunication Facilities.
The chassis should be installed where personnel
cannot interfere with cables and cords
connected to the chassis.
The chassis should be installed where cables
and rack location do not obstruct chassis
ventilation openings.
Location
See the electrical requirements in “BTI7814
Power” on page 40.
BTI7814 (BT8A78CH14)Electrical
See the electrical requirements in “BTI7802
Power” on page 48.
BTI7802 (BT8A78CH2-I02)
See the electrical requirements in “BTI7801
Power” on page 52.
BTI7801 (BT8A78CH1)
Always use ESD grounding devices when
handling components.
Electrostatic
5% to 95% non-condensingHumidity
15°C to +32°C; 59°F to +89.6°FBTI7814 (BT8A78CH14)Operating temperature
BTI7802 (BT8A78CH2-I02)
BTI7801 (BT8A78CH1)
-40°C to +70°C; -40°F to +158°FStorage temperature
Be familiar with the electrical and occupational safety guidelines for your country, for
example:
•
In the United States, reference the latest edition of The National Electrical Code (NEC),
and the latest guidelines of the U.S. Department of Labor, Occupational Safety &
Health Administration (OSHA).
•
In Canada, reference the latest edition of The Canadian Electrical Code (CEC), and the
latest guidelines of the Canadian Centre for Occupational Health and Safety (CCOHS).
27Copyright © 2019, Juniper Networks, Inc.