You have successfully completed this procedure.
Replacing the BTI7802 CAP
This topic describes how to remove and replace the Chassis Alarm Panel (CAP) on the
BTI7802 chassis.
The CAP is hot-swappable and can be replaced while the system is powered on and
operational.
NOTE: Ensure that you are familiar with the safety and electrical warnings
described in “BTI7802 Field-Replaceable Units (FRUs)” on page 193.
Tools Required
•
Number 2 Phillips screwdriver
1. Remove all cable or other obstructions.
2. Loosen the thumbscrew at the top of the module.
3. Carefully grip the handle. Gently pull the module out of the chassis.
4. Place the module in an antistatic bag or on a grounded antistatic mat.
5. Align the replacement CAP with the slot guides.
6. Gently push the module until it connects to the backplane.
Once the module is in place, the ACT LED turns solid green.
7. Carefully tighten the thumbscrew.
You have successfully completed this procedure.
Replacing the BTI7802 FAN2
Use this procedure to replace a 2-Slot Chassis Cooling Module on the BTI7802 chassis.
195Copyright © 2019, Juniper Networks, Inc.
Chapter 7: BTI7800 Series Field Replaceable Units (FRUs)