Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 165
5 Motor control (MCTRL)
5.4 V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Note!
87-Hz operation
4-pole asynchronous motors which are designed for a rated frequency of f = 50 Hz in star
connection can be operated in delta connection when being constantly excited up to f =
87 Hz.
•Advantages:
Higher speed-setting range
73% higher power output in case of standard motors
Motor current and motor power increase by the factor .
The field weakening range starts above 87 Hz.
Generally, this process can also be used with motors which have different numbers of
pole pairs. In case of 2-pole asynchronous motors, the mechanical limit speed must be
maintained.