9 Diagnostics & error management
9.6 Monitoring
642
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.6.2 Setting the error response
When a monitoring function responds, the response set for this monitoring function (TroubleQSP,
Warning, Fault, etc.) will be triggered.
• For many monitoring functions the response can be individually parameterised via parameters.
Tip!
The table in the chapter "Short overview (A-Z)
" contains the error messages for which the
response can be set.
( 653)
Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold (e.g. temperature)
has been exceeded.
• The corresponding preset threshold values can be changed via the following parameters:
Parameters Info
C00120
Setting of motor overload (I²xt)
C00123
Device utilisat. threshold (Ixt)
C00572
Brake resistor overload threshold
C00599
Motor phase failure threshold