Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 79
3 Commissioning
3.8 Commissioning of the "Table positioning" technology application
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
More detailed information on the technology application:
TA "Table positioning"
( 434)
Basic signal flow
( 435)
Internal interfaces | Application block "LA_TabPos"
( 439)
Process data assignment for fieldbus communication
( 458)
Terminal assignment of the control modes
( 449)
Setting parameters (short overview)
( 460)
Configuration parameters
( 461)
3.8.5 Save parameter settings safe against mains failure
In order to prevent parameter settings carried out in the device from being lost by mains switching,
you have to explicitly save the parameter set with mains failure protection in the device.
Save parameter set.
3.8.6 Enable inverter and test application
If the inverter is in the "SwitchedOn" state:
1. Enable inverter: Set terminal X5/RFR to HIGH level or close contact.
If there is no other active source for the controller inhibit, the inverter changes from the
"SwitchedOn
" status to the "OperationEnabled" status.
•The Diagnostics tab and C00158
display all active sources for the controller inhibit.
2. Select the respective control signals via the digital inputs (see sections below).
Stop!
Before stipulating a speed setpoint, check whether the brake in the form of a holding
brake on the motor shaft has been released!
Note!
If the controller is enabled at mains connection and C00142 has activated the "Inhibit at
power-on" auto-start option (Lenze setting), the inverter remains in the
"ReadyToSwitchOn
" state.
To be able to change to the "SwitchedOn
" status, the controller enable must be
deactivated first: set terminal X5/RFR to LOW level.
Note!
Observe the actual speed value (display in C00051) as well as the LED status displays.
( 624)