9 Diagnostics & error management
9.6 Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.6.3 AutoFailReset function
The AutoFailReset function serves to automatically reset the latching "Fault" and "TroubleQSP"
errors as well as the latching "WarningLocked" warning.
The "latching" term means that the effect on the inverter remains active even after the error cause
has been removed.
To reset latching errors and warnings, the following options are available:
Manual reset
with device command C00002/19
(activated by Low-High edge)
by a Low-High edge at the bResetFail input of the LS_DriveInterface
(the "FailReset" control
bit in the control word must be parameterised with a value of "1").
•Automatic reset
using the AutoFailReset function.
Overview of the relevant parameters
Parameters Info
C00184
Repetition time of the error reset processes
C00185 Time left until the next error reset process
C00186
Max. number of permissible unsuccessful error reset processes
When the number set is reached, the response parameterised in C00189
is executed.
C00187 Current number of unsuccessful error reset processes carried out
C00188
Configuration of the AutoFailReset function
•0: Off
•1: Fault + TroubleQSP
•2: WarningLocked
3: All locking
C00189
Response after max. number of unsuccessful error reset processes has been
reached
Greyed out = display parameter