Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 1468
17 Function library
17.1 Function blocks | L_PCTRL_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
17.1.134.6 Control functions
The process controller has various digital inputs for controlling the FB:
Designator
Data type
Information/possible settings
bInAct
BOOL
Deactivate process controller temporarily (stop)
Changes can be done online.
Display parameter: C00833/76
Note: This input is not interconnected in the LA_NCtrl application block.
TRUE The current output value is frozen.
The internal control algorithm is stopped.
However, a setpoint selected via input nNSet_a is still provided in
operating modes 0/1/4/5.
bIOff
BOOL
Switch off the I-component of the process controller
Changes can be done online.
Display parameter: C00833/77
TRUE The I component of the process controller is set to zero.
bPIDOff
BOOL
(from version 06.00.00)
Reset the entire PID controller
TRUE The I component of the controller is set to zero.
The controller output is set to zero.
The internal control algorithm is stopped.