5 Motor control (MCTRL)
5.5 V/f characteristic control - energy-saving (VFCplusEco)
176
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.5.1 Parameterisation dialog/signal flow
Proceed as follows to open the dialog for parameterising the motor control:
1. »Engineer« Go to the Project view and select the 8400 HighLine inverter.
2. Select the Application parameters tab from the Workspace.
3. Select the motor control "11: VFCplusEco: V/f energy-saving" from the Overview dialog box
in the Motor control list field:
4. Click the Motor control V/f Eco button to change to the Overview Motor control V/f dialog
box.
This dialog level only shows a simplified signal flow with the most important
parameters.
When you click the >>More details button in the left-most position, a signal flow with
more details/parameters is displayed.
Stop!
For adjustment, observe the thermal performance of the connected asynchronous
motor at low output frequencies.
Usually, standard asynchronous motors with insulation class B can be operated for
a short time with their rated current in the frequency range 0 Hz ... 25 Hz.
Contact the motor manufacturer to get the exact setting values for the max.
permissible motor current of self-ventilated motors in the lower speed range.
The nameplate data of the motor (at least rated speed and rated frequency) must be
entered if, instead of a standard motor, an asynchronous motor is used with the
following values:
•rated frequency 50 Hz (star) or
•rated frequency 87 Hz (delta) or
number of pole pairs 2