EasyManua.ls Logo

Lenze 8400 - Optimising Dynamic Performance and Field Weakening Behaviour

Lenze 8400
1590 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Motor control (MCTRL)
5.7 Sensorless vector control (SLVC)
200
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Speed controller reset time Ti
Apart from setting the P component, C00071/1
provides the possibility to take influence on the I
component of the PI controller.
Tip!
Value range recommended by Lenze for the setting of the reset time:
Ti = 20 ms … 150 ms
5.7.4.3 Optimising dynamic performance and field weakening behaviour
In the Lenze setting, the torque controller has been preset in such a way that robust and stable
operation with a moderate dynamic response is enabled over the entire speed range. Retrospective
optimisation of the controller parameters is not necessary.
A greater dynamic performance of the sensorless vector control can be achieved by reducing time
constant Ti of the speed controller (C00074/2
).
A greater dynamic performance of the field weakening function can be achieved by setting a time
constant 15 ms. This means for actual speeds above rated speed a better torque-speed-
characteristic in the field weakening range:
[5-11] Speed / torque characteristic diagram in the field weakening range
For Ti >15ms (see ), the actual speed value slightly drops in the field weakening range if the
load torque increases in the motor mode.
•For Ti 15 ms (see ), the speed remains stable in the field weakening range if the torque is
within the M/n characteristic field highlighted in grey.
Tip!
For applications with high dynamic performance and speed/torque accuracy requirements
in the field weakening range, we recommend a time constant Ti 15 ms.
In this case, the maximum torque should be limited via the nTorqueMotLimit_a and
nTorqueGenLimit_a process input signals to 1.5 x M
N
to ensure stable operation in the field
weakening range.
Parameters Info Lenze setting
Value Unit
C00073/2 SLVC: Vp torque controller 1.25
C00074/2
SLVC: Ti torque controller 30 ms
Torque controller time constant Ti > 15 ms
Torque controller time constant Ti 15 ms
10
n
N
n
N
M
N
M
N
MM
nn

Table of Contents

Other manuals for Lenze 8400

Related product manuals