Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 829
15 Parameter reference
15.2 Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00074
C00075
C00076
C00077
Parameter | Name:
C00074 | Reset time Imax/M controller
Data type: UNSIGNED_16
Index: 24501
d
= 5FB5
h
Reset time Ti of certain controllers for different motor control modes
Setting range (min. value | unit | max. value)
0 ms 9990
Subcodes Lenze setting Info
C00074/1 power-related (see table
)ms VFC: Ti Imax controller
C00074/2 power-related (see table
)ms SLVC: Ti torque controller
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00075 | Vp current controller
Data type: UNSIGNED_16
Index: 24500
d
= 5FB4
h
Gain factor Vp of the current controller for servo control (SC) and certain inverter functions (parameter
identification, flying restart circuit)
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically.
Setting range (min. value | unit | max. value) Lenze setting
0.00 V/A 500.00 power-related (see table
)
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00076 | Ti current controller
Data type: UNSIGNED_16
Index: 24499
d
= 5FB3
h
Reset time Ti of the current controller for servo control (SC) and certain inverter functions (parameter identification,
flying restart circuit)
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically.
Setting range (min. value | unit | max. value) Lenze setting
0.00 ms 500.00 power-related (see table
)
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00077 | SC: Vp field controller
Data type: UNSIGNED_16
Index: 24498
d
= 5FB2
h
Gain factor Vp of the field controller for servo control (SC)
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically.
Setting range (min. value | unit | max. value) Lenze setting
0.00 500.00 power-related (see table
)
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100