Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 157
5 Motor control (MCTRL)
5.4 V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4 V/f characteristic control (VFCplus)
In case of the V/f characteristic control (VFCplus), the motor voltage of the inverter is determined by
means of a linear or quadratic characteristic depending on the field frequency or motor speed to be
generated. The voltage follows a preselected characteristic.
Stop!
The V/f characteristic control is only suitable for asynchronous motors.
The following must be observed when operating drives with quadratic V/f
characteristic:
Please always check whether the corresponding drive is suitable for operation with
a quadratic V/f characteristic!
If you pump or fan drive is not suitable for operation with a square-law V/f
characteristic, we recommend using the energy-saving V/f characteristic control
(VFCplusEco). Alternatively, you can use the V/f characteristic control with linear
V/f characteristic or the sensorless vector control (SLVC) or servo control (SC).
For adjustment, observe the thermal performance of the connected asynchronous
motor at low output frequencies.
Usually, standard asynchronous motors with insulation class B can be operated for
a short time with their rated current in the frequency range 0 Hz ... 25 Hz.
Contact the motor manufacturer to get the exact setting values for the max.
permissible motor current of self-ventilated motors in the lower speed range.
If you select square-law V/f characteristics, we recommend setting a lower V
min
or
using the energy-saving V/f characteristic control (VFCplusEco).
The nameplate data of the motor (at least rated speed and rated frequency) must be
entered if, instead of a standard motor, an asynchronous motor is used with the
following values:
•rated frequency 50 Hz (star) or
•rated frequency 87 Hz (delta) or
number of pole pairs 2
Note!
When the auto DCB threshold (C00019) is set > 0 rpm, there is no torque at the motor
shaft in the lower speed range!
Automatic DC-injection braking (Auto-DCB)
( 268)