9 Diagnostics & error management
9.9 Error messages of the operating system
670
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PS04: Par. set Mci invalid [xx.0144.00004]
PS07: Par. memory module invalid [xx.0144.00007]
PS08: Par. device invalid [xx.0144.00008]
PS09: Par. format invalid [xx.0144.00009]
PS10: Memory module binding invalid [xx.0144.00010]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The parameter set saved to the communication module
is incompatible to the standard device.
• An incompatibility of the parameter set is caused e.g.
when the MCI module parameters in the memory
module do not match the plugged communication
module.
When the memory modules are replaced, observe the
compatibility:
• Not OK: Profibus V1.0 to EtherCAT V1.0
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The parameter set saved to the memory module is
invalid.
• The error occurs while loading the parameter set.
• The memory module plugged in the device lacks a
code or a code is incorrect.
Please contact Lenze.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The parameter set in the device is invalid.
• The error occurs while loading the parameter set.
• One code in the device is incorrect.
Please contact Lenze.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The code format is invalid.
• The error occurs while loading the parameter set.
Please contact Lenze.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
Device personalisation is active: The binding ID of the
memory module does not comply with the binding ID of
the inverter.
• Use memory module/inverter with matching binding
IDs.
• Contact machine manufacturer.
Note:
It is not possible for Lenze to modify a replacement
device via special accesses in such a way that it
cooperates with a personalised memory module.