Parameter Name / value range / [default seng] Info
0x4021:002
(PAR 606/002)
Process contr
oller speed operaon: Deceleraon me
(PID acc./dec.: PID deceleraon me)
0.0 ... [1.0] ... 3600.0 s
Deceleraon me for (temporary) speed-controlled drive control in
process controller mode.
This deceleraon me is eecve if process controller mode is acve
and a change-over to speed-controlled operaon has been eected
by the trigger set in 0x2631:045 (PAR 400/045).
The deceleraon me takes eect at the output of the process con-
troller.
0x4048
(PAR 601)
P component gain
(P-gain)
0.0 ... [5.0] ... 1000.0 %
Output frequency of the process controller per 1 % system deviaon.
100 % ≡ maximum frequency 0x2916 (P
AR 211).
0x4049
(PAR 602)
I component rese
t me
(I-deceleraon)
20 ... [400] ... 6000 ms
Reset me for system deviaon.
With the seng "6000 ms", the I component is deacvated.
The I component can also be deacvated via a trigg
er assigned in
0x2631:047 (PAR 400/047) of the "Inhibit process con
troller I-
component" 0x2631:047 (PAR 400/047) funcon.
0x404A
(PAR 603)
D component gain
(D-gain)
0.0 ... [0.0] ... 20.0 s
D component, does not respond to the rate of the system deviaon, but
only to its rate of change.
0x404B
(PAR 604)
Setpoint ramp (process controller)
(PID setp.ramp)
0.0 ... [20.0] ... 100.0 s
Acceleraon me and deceleraon me for the process controller set-
point, relang to the enre seng range of the process controller.
0x404C:001
(PAR 607/001)
Process controller inuence: Acceleraon me for
showing
(PID inuence: Show me)
0.0 ... [5.0] ... 999.9 s
If the trigger assigned in 0x2631:048 (PAR 400/048) of the "Acvate
process controller inuence ramp" funcon is TRUE, the inuence of the
process controller is shown by means of a ramp with the acceleraon
me set here.
0x404C:002
(PAR 607/002)
Process controller inuence: Deceleraon me for
masking out
(PID inuence: Mask out me)
0.0 ... [5.0] ... 999.9 s
If the trigger assigned in 0x2631:048 (PAR 400/048) of the "Acvate
process controller inuence ramp" funcon is FALSE, the inuence of the
process controller is hidden via a ramp with the deceleraon me set
here.
0x404D:001
(PAR 608/001)
Process contr
oller alarms: MIN alarm threshold
(PID alarms: PID min alarm)
-300.00 ... [0.00] ... 300.00 PUnit
Trigger threshold for the "MIN alarm" trigger.
The "MIN alarm" trigger is TRUE if the controlled variable fed back (in
process controller mode) is smaller than the threshold set here.
The trigger can be assigned to the relay, a digital output, or the NET-
WordOUT1 status word. 4
Conguraon of digit
al outputs ^
215
0x404D:002
(P
AR 608/002)
Pr
ocess controller alarms: MAX alarm threshold
(PID alarms: PID max alarm)
-300.00 ... [100.00] ... 300.00 PUnit
Trigger threshold for the "MAX alarm" trigger.
The "MAX alarm" trigger is TRUE if the controlled variable fed back (in
process controller mode) is greater than the threshold set here.
The trigger can be assigned to the relay, a digital output or the NET-
WordOUT1 status word. 4Conguraon of digital outputs ^ 215
0x404E:001
(PAR 605/001)
Se
tpoint limits (process controller): Minimum setpoint
(PID setp. limit: PID setp. min.)
-300.00 ... [-300.00] ... 300.00 PUnit
Minimum value of the process controller seng range.
0x404E:002
(PAR 605/002)
Setpoint limits (process controller): Maximum
setpoint
(PID setp. limit: PID setp. max.)
-300.00 ... [300.00] ... 300.00 PUnit
Maximum value of the process controller seng range.
0x2860:002
(PAR 201/002)
Standard setpoint sources: Process controller setpoint
source
(Standard setpoint: PID setpoint)
For possible sengs see descripon for
0x2860:002 (PAR 201/002). ^ 70
Selecon of the standard setpoint source for process controller mode.
The standard setpoint source is always acve in process controller
mode if no setpoint change-over to another setpoint source via corre-
sponding triggers/funcons is acve.
1 Keypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:002 (PAR 202/002)
Use the
and
navigaon k
eys to change the keypad setpoint
(also during running operaon).
Conguring the process controller
Basic process controller sengs
140