Parameter Name / value range / [default seng] Info
58 Device warning acve TRUE if warning is acve. Otherwise FALSE.
•
A warning has no impact on the operang status of the in
verter.
•
A warning is reset automacally if the cause has been eliminated.
59 Device fault acve TRUE if a fault is acve. Otherwise FALSE.
•
A fault deacvates control of the motor in the moment of its occur-
rence.
•
A fault is reset automacally if the cause has been eliminated.
60 Heatsink temperature warning acve TRUE if current heatsink temperature > warning threshold for tempera-
ture monitoring. Otherwise FALSE.
•
Displa
y of the current heatsink temperature in 0x2D84:001
(PAR 117/001).
•
Seng of the warning threshold in 0x2D84:002.
69 Reversal acve TRUE if reversal is acve. Otherwise FALSE.
•
Selecon of the trigg
er for the "Reversal" funcon in 0x2631:013
(PAR 400/013).
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
•
Display of the current output frequency in 0x2DDD (PAR 100).
•
Seng Frequency thresholdin 0x4005 (PAR 412).
4Frequency threshold for "Frequency threshold exceeded" trigger ^ 209
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz), irrespecve of the
operang mode. Otherwise FALSE.
•
Display of the curr
ent output frequency in 0x2DDD (PAR 100).
78 Current limit reached
TRUE if current motor current ≥ maximum current. Otherwise F
ALSE.
•
Display of the present motor current in 0x2D88 (PAR 104).
•
Seng for the maximum current in 0x6073 (PAR 324).
80 Follower signal (4 … 20 mA) lost TRUE if follower signal (4 … 20 mA) lower than 2 mA.
81 Error of analog input 1 TRUE if error detecon for analog input 1 has been acvated. Otherwise
FALSE.
The err
or detecon funcon can be congured via the following param-
eters:
•
Monitoring threshold 0x2636:008 (PAR 430/008)
•
Monitoring condion 0x2636:009 (PAR 430/009)
•
Monitoring response 0x2636:010 (PAR 430/010)
4Analog input 1 ^ 211
82 Error of analog input 2 TRUE if error
detecon f
or analog input 2 has been acvated. Other
wise
F
ALSE.
The err
or detecon funcon can be congured via the following param-
eters:
•
Monitoring threshold 0x2637:008 (PAR 431/008)
•
Monitoring condion 0x2637:009 (PAR 431/009)
•
Monitoring response 0x2637:010 (PAR 431/010)
4Analog input 2 ^ 213
83 Load loss TRUE if current motor current < threshold for load loss detecon for at
least the delay for load loss detecon. Otherwise F
ALSE.
•
Display of the present motor current in 0x6078 (PAR 103).
•
Seng Threshold in 0x4006:001 (PAR 710/001).
•
Seng Deceleraonin 0x4006:002 (PAR 710/002).
4Load loss detecon ^ 158
104 Local control acve TRUE if local keypad control ("LOC") acve. Otherwise FALSE.
105 Remote control acve TRUE if remote con
trol ("REM") via terminals, network, etc. acve. Oth-
erwise FALSE.
106 Manual setpoint selecon acve TRUE if manual setpoint selecon ("MAN") via keypad acve. Otherwise
FALSE.
•
Selecon of the trigger for the "Setpoint = Keypad" funcon in
0x2631:016 (PAR 400/016).
107 Automac setpoint selecon acve TRUE if automac setpoint selecon ("AUTO") via terminals, network,
etc. acve. Otherwise FALSE.
Flexible I/O conguraon
Controller enable, starng & stopping, reversal
189