Parameter Name / value range / [default seng] Info
0x2631:002
(PAR 400/002)
Funcon assignment: Start enable
(Funcon lis
t: Start enable)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Start enable" funcon.
Trigger = FALSE-TRUE edge: Drive is started in forward rotang direcon
(CW) if the following condions are fullled:
•
Controller is enabled and no error or quick st
op are acve.
•
No other start command is congured (start-forwards/start-back-
wards/run-for
wards/run-backwards = "Not connected [0]").
Trigger = TRUE-FALSE edge: drive is stopped again.
Notes:
•
If the controller enable is set = "Constant TRUE [1]", the only permissi-
ble trigger for this funcon is a digital input (otherwise the error mes-
sage "Connected incorrectly" appears).
•
The stop method can be selected in 0x2838:003 (PAR 203/003).
•
The funcon also serves to realise an automac start aer switch-on.
4Starng performance ^
72
11 Digital input 1 State of X3/DI1, taking an inversion set in 0x2632:001 (PAR 411/001) into
consideraon.
0x2631:003
(PAR 400/003)
Funcon assignment: Quick stop
(Funcon list: Quick stop)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Quick stop" funcon.
Trigger = TRUE: "Quick stop" funcon acvated.
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
•
The "Quick stop" funcon brings the motor to a standsll within the
deceleraon me set in 0x291C (PAR 225).
•
The "Quick stop" funcon has a higher priority than the "Start enable"
funcon.
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:004
(PAR 400/004)
Funcon assignment: Reset error
(Funcon list: Reset error)
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Reset error" funcon.
Trigger = FALSE-TRUE edge: acve error is reset (acknowledged) if the
error cause has been eliminated.
Trigger = FALSE: no acon.
Notes:
•
Aer reseng the error, a new enable/start command is required to
restart the drive.
12 Digital input 2 State of X3/DI2, taking an inversion set in 0x2632:002 (PAR 411/002) into
consideraon.
0x2631:013
(PAR 400/013)
Funcon assignment: Reversal
(Funcon list: Reversal of rot. dir.)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Reversal" funcon.
Trigger = TRUE: the setpoint specied is inverted (i. e. the sign is inver-
ted).
Trigger = FALSE: no acon / deacvate funcon again.
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (PAR 411/003) into
consideraon.
0x2631:018
(PAR 400/018)
Funcon assignment: Preset v
al. selecon bit 0
(Funcon list: Preset b0)
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Preset val. selecon bit 0" funcon.
Selecon bit with the valency 20 for the bit-coded selecon and acva-
on of a parameterised setpoint (preset value).
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
14 Digital input 4 State of X3/DI4, taking an inversion set in 0x2632:004 (PAR 411/004) into
consideraon.
0x2631:019
(PAR 400/019)
Funcon assignment: Preset val. selecon bit 1
(Funcon list: Preset b1)
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Preset val. selecon bit 1" funcon.
Selecon bit with the valency 21 for the bit-coded selecon and acva-
on of a parameterised setpoint (preset value).
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
15 Digital input 5 State of X3/DI5, taking an inversion set in 0x2632:005 (PAR 411/005) into
consideraon.
Commissioning
Parameter seng
Funcon assignmen
t of the inputs and outputs
22