EasyManua.ls Logo

MKS 146C - Page 198

MKS 146C
358 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter Six: Operation in Tuning Mode How To Ad
j
ust Gain
175
2. Enter the number of the recipe (1 through 4), which is to have the Gain setting adjusted.
The system responds by accepting the recipe number.
Note
If the
MANUAL
or
HOLD
legend is displayed,
and
the right display
shows the Edit Reci
p
e
p
arameter (E1, E2, E3, or E4), the left dis
p
la
y
will
blink. The left display is flashing the current control valve position.
Since we want to edit a recipe, you may ignore the blinking left display
and proceed to the next step.
3. Press the [
OFF
/
GAIN
] key,
OR
scroll through the Tuning Mode parameters with the
arrow keys until the
GAIN
legend is displayed, then press the [
ENTER
] key.
The system responds by changing the window parameters, and causing the right display
to blink.
4. Enter a value for Gain between 0.002 and 10,000 (the default is 10).
A. If the Gain value is already correct, press the [
ENTER
] key.
B. If the Gain value is incorrect, use the [
ZERO
/
EXP
] , [+/-] , and numeral keys to
enter the correct Gain value, then press the [
ENTER
] key.
The system responds by accepting the Gain value.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents