Chapter Seven: Operation in Setup Mode Code 13x: How To Ad
j
ust Softstart for Control
233
1. Repeatedly press the [
DISPLAY MODE
] key until the 146 unit is in Setup Mode.
The system responds by scrolling through modes.
2. Use the arrow keys to scroll to the
CODE
legend.
The system responds by causing the left display to blink.
3. Enter the number
13x
(where
x
represents a recipe number), and press the [
ENTER
]
key.
The system responds by displaying the appropriate parameters for code 13x, and causing
the main display to blink.
4. Enter the softstart speed value. The range is 1 to 99 seconds, and the default is 10
seconds.
A. If the display is correct, press the [
ENTER
] key.
B. If the display is not correct, enter the correct softstart speed value (1 to 99), then
press the [
ENTER
] key.
The system responds by accepting the softstart speed value, and causing the right display
to blink.
Note
The softstart speed is common to
all
recipes.
5. Select On or Off in the right display (the default is Off).
A. If the display is correct, press the [
ENTER
] key.
B. If the display is not correct, use the [
ON
/
LEAD
] or [
OFF
/
GAIN
] key to enable or
disable the Softstart Control feature for the selected recipe, then press the [
ENTER
]
key.
The system responds by enabling or disabling the Softstart Control feature for the
selected recipe.