8 Operation
Maschinenfabrik Reinhausen GmbH 2020168 3587317/21 ENTAPCON
®
Circuit 3-D
L1
L2
L3
VTVT
CT
UI
L1 L2 L3 N k1 l1 k2 l2 k3 l3
Three-phase voltage measurement, single-phase current measurement.
The voltage transformers are connected between the phases.
The current transformer is connected to phase L2.
Parameter Option
Voltage-transformer circuit -
Current-transformer circuit -
Phase angle correction -150°
UI measuring channels 3-ph. voltage, 1-ph. current
Measurement mode Phase-phase
Table55: Circuit 3-D
Circuit 3-E
L1
L2
L3
VTVT
CT
UI
L1 L2 L3 N k1 l1 k2 l2 k3 l3
Three-phase voltage measurement, single-phase current measurement.
The voltage transformers are connected between the phases.
The current transformer is connected to phase L3.
Parameter Option
Voltage-transformer circuit -
Current-transformer circuit -
Phase angle correction 90°

Table of Contents