8 Operation
Maschinenfabrik Reinhausen GmbH 2020170 3587317/21 ENTAPCON
®
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phase and neutral
conductor.
▪ The current transformer is connected to phase L2.
Parameter Option
Voltage-transformer circuit 3 Ph phase voltage
Current-transformer circuit 3 Ph phase current
Phase angle correction -120°
UI measuring channels 3-ph. voltage, 1-ph. current
Measurement mode Phase-neutral
Table58: Circuit 3-G
Circuit 3-H
L1
L2
L3
N
UI
VTVT
VT
CT
L1 L2 L3 N k1 l1 k2 l2 k3 l3
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phase and neutral
conductor.
▪ The current transformer is connected to phase L3.
Parameter Option
Voltage-transformer circuit 3 Ph phase voltage
Current-transformer circuit 3 Ph phase current
Phase angle correction 120°
UI measuring channels 3-ph. voltage, 1-ph. current
Measurement mode Phase-neutral
Table59: Circuit 3-H