EasyManua.ls Logo

MR TAPCON - Page 211

MR TAPCON
334 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Operation
Maschinenfabrik Reinhausen GmbH 2020 2113587317/21 EN TAPCON
®
You can set the following parameters for each limit value:
Hysteresis limit value: Specification as a percentage relative to the de-
sired voltage value.
Delay time limit value
Behavior If the measured value is higher than the upper limit or lower than the lower
limit, the device triggers the Upper bandwidth limit value / Lower bandwidth
limit value message.
The "Function monitoring" function is used to detect long periods when val-
ues are above or below the bandwidth. Long periods when values are above
or below the bandwidth indicate a problem with the device function because
the device is not able to correct the control deviation.
If the value is above or below the set bandwidth [Page 151], the Function
monitoring event is displayed after the set delay time for function monitoring
has elapsed. The event is automatically acknowledged as soon as the mea-
sured value is back within the set bandwidth.
The following parameters are available for setting function monitoring:
Function monitoring
Hysteresis
Delay time
Settings
U bandwidt...ing
Name Value
Function monitoring Auto and Manual
Hysteresis 0.0%
Delay time 15min
Lower bandwidth hysteresis 0.1%
Lower bandwidth delay time 2s
Upper bandwidth hysteresis 0.1%
Upper bandwidth delay time 2s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin 23.09.2020 09:23
Figure145: U bandwidth monitoring
1. Go to Settings > Parameters > On-load tap-changer regulator > U
bandwidth monitoring.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.
Also refer to
2 Current monitoring [202]

Table of Contents

Related product manuals