14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020 3033587317/21 EN TAPCON
®
Parameter Setting range Factory setting Current setting
Settings > Parameters > Parallel operation
Activate parallel operation Off, On Off
Parallel operation method Circulating reactive cur-
rent; Master; Follower; Au-
tomatic tap synchroniza-
tion; Power factor
Circulating reactive current
CAN bus address 0...16 0
Circulating reactive current sensi-
tivity
0.0...100.0% 0.0%
Circulating reactive current block-
ing limit
0.5...20.0% 20.0%
Master/follower current blocking Off, On Off
Maximum tap difference 1...4 1
Error, if no communication
present
No error, Error No error
Behavior for communication fail-
ure
No error, Error No error
Behavior, if no communication
present
Independent regulation,
auto blocking, cosφ inter-
polation
Independent regulation
Delay time par. op. error mes-
sage
1...30 s 5s
Settings > Parameters > Retrofit TAPCON®2xx
Retrofit TAPCON® 2xx Off, On Off
Settings > Parameters > Voltage monitoring
U< relative/absolute Relative, Absolute Relative
U< [V] 40.0...160.0 V 90.0 V
U< [%] 60.0...100.0% 90.0%
U< hysteresis 0.0...10.0 V 0.0 V
U< delay time 0.5...60.0 s 0.5s
U< behavior Off, High-speed return U+,
Auto blocking, Auto/man-
ual blocking
Off
U<< relative/absolute Relative, Absolute Relative
U<< [V] 40.0...160.0 V 80.0 V
U<< [%] 60.0...100.0% 80.0%
U<< hysteresis 0.0...10.0 V 0.0 V
U<< delay time 0.5...60.0 s 0.5s
U<< behavior Off, High-speed return U+,
Auto blocking, Auto/man-
ual blocking
Off