14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020 3093587317/21 EN TAPCON
®
Parameter Setting range Factory setting Current setting
Settings > Parameters > DNP3 (optional)
DNP3 type
2
TCP, Serial In accordance with order
Serial interface
2
RS232, RS485 In accordance with order
Baud rate
2
9.6...115.2 kilobaud 9.6 kilobaud
IP address
2
0.0.0.0...255.255.255.255 192.168.10.254
Subnet mask
2
0.0.0.0...255.255.255.255 255.255.255.0
Gateway address
2
0.0.0.0...255.255.255.255 0.0.0.0
TCP port
2
0...65,535 2,404
Number of databits
2
5...8 8
Parity
2
None, Even, Odd In accordance with order
Number of stop bits
2
1...2 1
Device address
2
1...65,519 1
Target address
2
1...65,519 1
Unsolicited messages
2
On, Off Off
Number of unsolicited retries
2
1...100 3
Indefinite unsolicited retries
2
On, Off Off
Timeout for unsolicited mes-
sages
2
1...60 s 5s
Timeout for response confirma-
tions
2
1...60 s 5s
User ID code
2
- TAPCON
Settings > Parameters > Time synchronization
Time synchronization via SNTP Off, On Off
SNTP time server 0.0.0.0...255.255.255.255 0.0.0.0
Activate second time server Off, On Off
SNTP time server 2 0.0.0.0...255.255.255.255 0.0.0.0
Synchronization interval 1...86,400 s 900s
Reference time UTC, Local UTC
Time zone UTC-11 h...UTC+12 h UTC+01:00 h
Settings > Parameters > Mean value memory
Mean value interval 1...8,640 s 1 s
Settings > Parameters > Link digital outputs
Generic digital output 1
1
- 500
Generic digital output 2
1
- 500
Generic digital output 3
1
- 500
Generic digital output 4
1
- 500
Generic digital output 5
1
- 500

Table of Contents