15-13
WR903 FP0R
R9032
COM port
communication mode
flag
-
Turns on when the general-purpose communication function
is being used
- Goes off when the MEWTOCOL-COM or the PLC link
function is being used.
R9033
Print instruction
execution flag
Off: Printing is not executed.
On: Execution is in progress.
R9034
RUN overwrite
complete flag
Goes on for ony the first scan following completion of a rewrite
during the RUN operation.
R9037
COM port
communication error
flag
- Goes on is a transmission error occurs during data
communication.
- Goes off when a request is made to send data, using the
R9038
done flag during
general purpose
- Turns on when the terminator is received during general -
purpose serial communication.
R9039
transmission done
flag during general-
purpose serial
- Goes on when transmission has been completed in general-
purpose serial communication.
- Goes off when transmission is requested in general-purpose
serial communication.
R903E
done flag during
general purpose
- Turns on the terminator is received during general -purpose
serial communication.
R903F
transmission done
flag during general-
purpose serial
- Goes on when transmission has been completed in general-
purpose serial communication.
- Goes off when transmission is requested in general-purpose
serial communication.
A: Available, N/A: Not available
Note) R9030 to R9030F can be changed during 1 scan.