11
/
2017 Page 79 5IN2413 B
Quick keys Parameter Default Range

Bell Delay
00 minutes/seconds
0090
minutes/seconds
The time delay before the keypad sounder and the external sounder operate
after the onset of an alarm.

Switch Aux Break
10 seconds
0090 seconds
The time that the power supplied to the system's smoke detectors through
the programmable output is interrupted during a user-initiated smoke
detector reset, typically performed after a fire alarm or automatically when
the fire verification is defined in the system control (see Double Verification
of Fire Alarms
, page 85 for additional details).
Note
This feature is supported through any programmable output that is defined
as Switch AUX.

Wireless
Specifies the time intervals relating to the operation of the wireless module

Jamming Time
None
None, 10, 20 or
30 seconds
Specifies the period of time that the system's wireless module tolerates
unwanted radio frequencies capable of blocking (jamming) signals produced
by the system's transmitters. Once the specified time is reached, the main
panel sends a report code to the alarm receiving center (see Appendix E:
Monitoring Station Report Codes, page 235 Jamming faults).
NONE 10 SEC 20 SEC 30 SEC
NONE: No jamming will be detected or reported.
Note
Different sounds will be produced when jamming is detected, depending on
the defined Audible Jamming time

RX Supervise
0 0
7 hours
Specifies how often the system expects to get a signal from the system’s
transmitters. If a signal from a zone is not received during the specified time
the zone will be regarded as lost, the system will send a report code to the
monitoring station, and the system status will be "Not Ready."
Note
Setting to 0 hours disables supervision. It is recommended to set the
supervision time to a minimum of 3 hours