System Controls Advanced
Quick keys Parameter Default Range
Advanced
This section refers to the advanced controls in the system.
Double Verification of
Fire Alarms
No Yes/No
YES: Implemented on detection of smoke or fire for verification. Power to
the smoke detector(s) in the affected zone is cut off and restored after the
time defined in the Switch Aux Break delay (
Switch Aux Break, page
79). If a subsequent detection occurs in the same zone within one minute
at the end of the Switch Aux time, the system emits a fire alarm.
NO: No fire alarm verification takes place.
Alarm Zone Expander
Cut
No Yes/No
YES: Produces an alarm if the communication between the main panel and
any expander is lost. A report is transmitted to the monitoring station.
NO: No alarm occurs. The system, however, produces a local trouble
indication.
Code Grand Master
No Yes/No
YES: Only a user with the Grand Master authority level can change all user
codes, along with the time and date.
NO: Grand Master as well as those with the Master authority level can
change their own user codes and all codes of those with lower authority
levels – in addition to allowing changing the time and date. Also enables
those with User and Unbypass authority levels to change their own codes.
Area
No Yes/No
Changes the system operation to area instead of partition, which then
changes only the operation of a common zone.
YES: When selected, the following apply:
• A common zone will be armed after any partition is armed.
• A common zone will be disarmed only when all partitions are
disarmed.
NO: When selected, the following apply:
• A common zone will be armed only when all partitions are armed.
• A common zone will be disarmed when any partition is disarmed.