Configuration Options
3-47
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
• Address space
on the PROFIBUS DP (depends on the DP master)
-- IM151-1 BASIC interface module supports a maximum of 88 input bytes and
88 output bytes.
-- IM151-1 STANDARD and IM151-1 FO STANDARD interface modules
support:
-- maximum 128 input bytes and 128 output bytes
(up to 6ES7 151-1AA03-0AB0 or 6ES7 151-1AB02-0AB0)
-- maximum 244 input bytes and 244 output bytes
(up to 6ES7 151-1AA04-0AB0 or 6ES7 151-1AB03-0AB0)
-- The IM151-1 HIGH FEATURE interface module supports a maximum of 244
input bytes and 244 output bytes.
on the PROFINET IO
-- The IM151-3 PN interface module supports a maximum of 256 input bytes
and 256 output bytes.
• Power modules: Maximum configuration per potential group
Table 3-16 Maximum configuration per potential group
Power modules
Maximum
current-carrying
capacity
Connectable modules
PM-E 24 VDC power
module
10A The number of modules that can be
connected depends on the total current of
all the modules in this potential group.
This must not exceed 10 A in total. The
total current is decisively affected by the
PM-E power module
24..48 VDC
10A
g
ta
output mo
u
es:
•
2DO 24 VDC/0.5 A Standard
•
2DO 24 VDC/0.5 A High Feature
•
4DO 24 VDC/0.5 A Standard
•
4DO 24 VDC/0.5 A High Feature
PM-E power module
24..48 VDC/
24..230 VAC
10 A (24 VDC)
8 A (120/230 VAC)
•
2DO 24 VDC/2 A Standard
•
2DO 24 VDC/2 A High Feature
•
4DO 24 VDC/2 A Standard
•
4DO 24 VDC/2 A High Feature
•
2DO 24-230 VAC/2 A
• Number of identifiers: one identifier per module (max. 63 identifiers)
• You can use the ET 200S with DP masters with a diagnostic frame length of 32
bytes because you can set the length of the diagnostic frame in all the interface
modules (see Sections 6.1.6.2 and 8.1).