Wiring and Fitting
5-10
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
5.4.3 Wiring terminal modules with Fast Connect
Features
In the case of terminal modules with Fast Connect, the individual wires are
attached using a quick connection method that requires no stripping.
Fast Connect is a connection method that requires no preparation (i.e. the
conductor does not have to be stripped).
Each terminal of the terminal module with Fast Connect has a test opening (for
measuring the voltage, for example). The test opening is suitable for test
probes with a maximum diameter of 1.5 mm.
Wire end ferrules are not permitted.
Diagram of the Fast Connect terminal module
Locking mechanism closed (the cable is connected)
Locking mechanism open (the cable can be inserted)
Opening for 1 conductor: 0.5 ... 1.5 mm
2
Opening for measurement, testing: max. 1.5 mm
Terminal module
Fast Connect
Figure 5-4 Block diagram of the terminal module with Fast Connect
Prerequisites
Adhere to the wiring rules.
Tool required
3 mm screwdriver