Wiring and Fitting
5-7
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
5.4 Wiring the ET 200S
Section Description Page
5.4.1 Wiring a terminal module with screw-type terminals 5-8
5.4.2 Wiring a terminal module with spring terminals 5-8
5.4.3 Wiring a terminal module with Fast Connect 5-10
5.4.4 Wiring terminal modules 5-13
5.4.5 Wiring the IM151-1 BASIC, IM151-1 STANDARD and
IM151-1 HIGH FEATURE interface modules
5-18
5.4.6 Wiring the IM151-3 PN interface module 5-19
5.4.7 Wiring the IM151-1 FO STANDARD interface module 5-21
Wiring rules for the ET 200S
Wiring rules for ... Interface module
(supply voltage)
Terminal modules
(spring a nd
screw-type
terminals)
Terminal modules
(Fast Connect)
Connectable wire cross-
sections for rigid lines
No 0.14 to 2.5 mm
2
0.5to1.5mm
2
Connectable
wire
Without wire
end ferrule
0.25 to 2.5 mm
2
0.14 to 2.5 mm
2
0.5to1.5mm
2
cross-sections
for flexible lines
With wire end
ferrule
0.25 to 1.5 mm
2
0.14 to 1.5 mm
2
-- -- --
Number of wires per connection 1oracombinationof2wiresupto
1.5 mm
2
(sum)inacommonwireendferrule
1
Maximum external diameter of
the wire’s insulation
∅ 3.8 mm ∅ 3.1 mm at 1.5 mm
2
∅ 3.8 mm
at 2.5 mm
2
∅ 3.2 mm
at 1.5 mm
2
r
pp
ng
eng
o
ew
res
mm -- -- --
Wire end
ferrules to
DIN 46228
Without
insulating
collar
Design A,
8to12mmlong
Design A,
up to 12 mm long
-- -- --
With
insulating
collar 0.25 to
1.5 mm
2
Design E, up to 12 mm long -- -- --