Analog output module error types
Table 6-15 Analog output module error types
Analog output
modules
Error type Meaning Remedy
2AO U
Standard
2AO U
High
Feature
2AO I
Standard
2AO I
High
Feature
16
D
10000:
Parameter
assignment
error
Module cannot use the
parameter for the channel:
Inserted module does not
match the one configured.
Parameter assignment error.
Correct the configuration
(compare actual and
desired configuration).
Correct the parameter
assignment (parameter
assignment of wire break
diagnosis only with the
permitted measuring
ranges).
9
D
01001: Error Internal module error has
occurred (diagnostic
message on channel 0
applies to the whole
module).
Replace the module.
-- -- -- 1
D
00001:
Short-circuit
Short circuit of the actuator
supply.
Correct the process wiring.
-- -- -- 2AO I
Standard
2AO I
High
Feature
6
D
00110: Wire
break
Line to the actuator
interrupted.
Correct the process wiring.
1SSI
Table 6-16 1SSI
Error type
Meaning Remedy
1
D
00001: Short-circuit Short circuit of the supply to the
absolute position encoder.
Correct the process wiring.
9
D
01001: Error Internal module error occurred.
Load voltage from the power
module is too low.
Replace the module.
Correct the process wiring.
Check the load voltage.
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Adjust the parameter
assignment.
26
D
11010: External error/fault Start/stop bit error (absolute
sensor error): Wire break in the
sensor cable or sensor cable is
not connected. Sensor type,
transmission rate, and monoflop
time do not correspond to the
sensor connected;
programmable sensors do not
correspond to the settings on the
1SSI EM. Sensor is defective or
there are faults.
Replace the sensor; correct the
process wiring.
Correct the parameter settings