Commissioning and Diagnostics
6-45
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
2Pulse
Table 6-20 2PULSE
Error type
Meaning Remedy
1
D
00001: Short-circuit Short circuit of the sensor
supply or the actuator.
Check the wiring to the
momentary-contact switches
and the actuators. Correct the
process wiring.
9
D
01001: Error Internal module error occurred. Replace the module.
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Adjust the parameter
assignment.