Brief Instructions on Commissioning ET 200S
2-12
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Prerequisites
• You must have set up an S7 station consisting of a power supply module and
an I/O controller (for example, CPU 317-2 PN/DP). A CPU 317-2 PN/DP was
used as the I/O controller in this example.
• STEP 7 (V 5.3 with ServicePack 1 or higher) is fully installed on your
programming device (PG). You must be familiar with STEP 7.
• The programming device is connected to the PROFINET IO.
Installation
1. Mount the rail (35 mm x 7.5 mm or 15 mm) with a length of at least 210 mm on
a solid base.
2. Install the various modules on the rail beginning on the left (hook on, swing in,
move to the left). Adhere to the following sequence:
-- IM151-3 PN interface module
-- TM-P15N23-A1 terminal module
-- 4 x TM-E15N24-A1 terminal modules
-- TM-P15N23-A1 terminal module
-- 4 x TM-E15N24-A1 terminal modules
-- Terminating module
Wiring and Fitting
1. Wire the ET 200S as shown below:
2
3