EasyManua.ls Logo

Siemens SIMATIC ET 200S - Block Diagram of the 2 AI U High Feature

Siemens SIMATIC ET 200S
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-48
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Block diagram
ADC
24V
L+
1M
1
2
5
6
P1
P2
MUX
M
ANA
Backplane bus
ET 200S
backplane bus
interface
connection
Figure 12-8 Block diagram of the 2AI U High Feature
Technical data
Dimensions and weight
Dimensions W x H x D
(mm)
15 x 81 x 52
Weight Approx. 40 g
Module-specific data
Supports clock
synchronized mode
No
Number of inputs 2
Cable length
shielded max. 200 m (164 ft)
Voltages, currents, electrical potentials
Rated load voltage L+ (from
power module)
24 VDC
Polarity reversal
protection
Yes
Electrical isolation
Between the channels
and backplane bus
Yes
Between the channels
and load voltage L+
Between the channels
and PE
Yes
Yes
Between the channels No
Permitted potential
difference
Between the channels 140 VDC/100 VAC
Isolation tested 500 VDC
Current consumption
with load voltage L+ max . 5 3 mA
Power loss of the module Typical 0.85 W
Status, interrupts, diagnostics
Diagnostic functions
Group error red LED ”SF”
Diagnostic function can
be read (wire-break
diagnostics not
supported in this
module)
Yes

Table of Contents