Configuration Options
3-32
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
3. Carry out settings on the DP slave:
”Object Properties of the DP slave > ”Clocking” tab
-- Enable ”Synchronize DP slave with DP cycle”.
-- Enter the times Ti and To (if ”Times Ti and To same for all slaves” has not
been set on the DP master system). Recommendation: Accept the default
settings for Ti and To.
-- Select the electronic modules to be synchronized, and assign them on the
”Addresses” tab to the partial process image defined in the CPU.
General
information
Time Ti (read process values):
(min = 4.2500 ms; max = 4.2500
ms)
3.5000 Time base:ms ms
Time Ti (read process values):
(min = 1.0000 ms; max = 1,000 ms)
3.5000 Time base:ms ms
Synchronize DP slave to equidistant DP cycle (the same Ti/To for all slaves)
Properties -- DP slave
Equidistant DP cycle:
(min = 6.072 ms; max = 32.000 ms)
8.000 ms
Slave
parameters
Clocking
Module Clocked operation
Slot/name
(1) 2DI 24 VDC HF
(2) 4DI 24 VDC HF
(3) 2AI 2WIRE HS
(4) 2AI 4WIRE HS
OK Cancel Help
Figure 3-8 DP slave properties dialog box
Note
If you choose ”Clocking” from the ”Edit menu, a configuration overview of the
clocked modules appears.