Installation
4-6
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
4.3 Installing the TM-P and TM-E terminal modules
Features
The terminal modules receive the I/O modules and power modules.
The terminal modules can be prewired (without I/O modules).
All the terminal modules must be installed to the right of the interface module.
Prerequisites
The rail must be installed.
Tool required
3 mm screwdriver
Installing the terminal module
1. Hang the terminal module on the rail.
2. Tip the terminal module back until you hear the locking mechanism engage.
3. Move the terminal module to the left until you hear it snap into place at the
previous interface module (if already installed) or the terminal module.
1
2
3
Figure 4-3 Installing the terminal module