Digital Electronic Modules
11-4
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for digital output modules
Table 11-3 Parameters for digital output modules
2DO 24
VDC/
0.5A High
Feature
2DO 24--230
VAC/
1A
2RONONC
24--48 VDC/5 A
24--230 VAC/5 A
2DO/ 4DO
24 VDC/
0.5 A ST
Value range Default
Effective
2DO 24
VDC/
2A High
Feature
2RO NO
24--120 VDC/
5 A 24--230
VAC/
5A
2DO/ 4DO
24 VDC/
2AST
setting range
Response at CPU/master STOP -- -- --
•
apply
substitute
value
•
hold last
value
apply
substitute
value
Module
Substitute value
1)
-- -- --
•
”0”
•
”1”
”0” Channel
-- -- --
•
disable
•
enabled
disable Module
Diagnosis:
Wire break
2)
-- -- --
•
disable
•
enabled
disable Channel
Diagnosis:
Short circuit
as per M
-- -- --
•
disable
•
enabled
disable Channel
1)
Ifthe interface module is withoutpower, the digital output module does not output substitute values. Output
value = 0.
2)
Wire break is only detected when the output is switched off.
Process alarm
This parameter enables the process interrupts for the module.
Input delay
Signal interference can be suppressed with this parameter . Changes in the signal
are only detected after the specified time.
Trigger for process interrupt, rising edge
This parameter can be used in channels to enable a process interrupt with a rising
edge (a signal status change).