Wiring and Fitting
5-19
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
5.4.6 Wiring the IM151-3 PN interface module
Features
Connect the supply voltage and bus connection plug to the IM151-3 interface
module.
Prerequisites
Wire the interface module with the supply voltage switched off.
Adhere to the wiring rules (see Section 5.4).
Tool required
3 mm screwdriver
Industrial Ethernet Fast Connect Stripping Tool (6GK1 901-1GA00)
(stripping tool for Industrial Ethernet Fast Connect installation lines)
Required accessories
PROFINET connector conforming to the specifications in the
PROFINET Installation Guide
Industrial Ethernet Fast Connect installation lines
The following are suitable:
-- Fast Connect Standard Cable 6XV1 840-2AH10
-- Fast Connect Trailing Cable 6XV1 840-3AH10
-- Fast Connect Marine Cable 6XV1 840-4AH10
Installing bus terminal connector
Install the PROFINET connector in accordance with the directions in the
PROFINET Installation Guide.

Table of Contents