Analog Electronic Modules
12-13
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Measuring range for thermocouple type K
Table 12-18 SIMATIC S7 Format: Measuring range type K in °C and °F
Units
Units
Type
in °C
decimal hexa
decimal
Type
in °F
decimal hexa
decimal
Area
> 1622,0 32767 7FFF
H
> 2951,6 32767 7FFF
H
Overflow
1622,0
:
1372,1
16220
:
13721
3F5C
H
:
3599
H
2951,6
:
2501,7
29516
:
25062
734C
H
:
61B9
H
Overshoot range
1372,0
:
--270,0
13720
:
--2700
3598
H
:
F574
H
2501,6
:
--454,0
25061
:
--4540
61B8
H
:
EE44
H
Nominal range
< --270,0 -- 32768 8000
H
< --454,0 -- 32768 8000
H
Underflow
Measuring range for thermocouple type L
Table 12-19 SIMATIC S7 Format: Measuring Range Type L in °C and °F
Units
Units
Type L
in °C
decimal hexa
decimal
Type L
in °F
decimal hexa
decimal
Area
> 1150,0 32767 7FFF
H
> 2102,0 32767 7FFF
H
Overflow
1150,0
:
900,1
11500
:
9001
2CEC
H
:
2329
H
2102,0
:
1652,1
21020
:
16521
521C
H
:
4089
H
Overshoot range
900,0
:
--200,0
9000
:
--2000
2328
H
:
F830
H
1652,0
:
--328,0
16520
:
--3280
4088
H
:
F330
H
Nominal range
< --200,0 --32768 8000
H
< --328,0 --32768 8000
H
Underflow