Commissioning and Diagnostics
6-22
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
6.1.4 Diagnostic messages of the electronic modules
Actions after a diagnostic message in DPV0 operation
The error is entered in the diagnostic frame in the channel-specific diagnosis:
The SF LED on the interface module comes on.
Several simultaneous diagnostic messages are possible.
Actions after a diagnostic message in DPV1 operation
Every diagnostic message leads to the following actions:
Diagnoses can be reported as diagnostic interrupts in DPV1 operation.
After a diagnostic message this is:
-- Entered in the diagnostic frame as a diagnostic interrupt block
(always only one interrupt)
-- Stored in the diagnostic buffer of the CPU
The SF LED on the interface module comes on.
The OB 82 is called. If OB 82 is not available, the CPU goes into STOP mode.
Acknowledgment of the diagnostic interrupt (following this a new interrupt is
possible).
Causes of Errors and Remedies
The causes of the errors and the action to be taken when specific diagnostic
messages appear are described in Section 6.1.6.8.