Configuration Options
3-30
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Procedure for parameterizing clocking
1. Carry out settings on the CPU:
”Object Properties of the CPU> Clocked interrupts” tab
-- Set the CPU clocked interrupt
-- Select the DP master system used.
-- Select the desired partial process image.
Memory Interrupts Interrupts Cyclic interrupts
Diagnostics/
clock
General
information
Startup Clocked interrupts Cycle / clock memory Retentivity
OB 61:
Priority
DP master-
systemno.
Partial process
image(s) (e. g.: 1.4)
Time lag
1 1 ms
D
efault
3.000
25
25
Time-of-day
interrupts
Figure 3-6 Clocked interrupts dialog box
2. Carry out settings on the DP master system:
”Object Properties of the DP master > ”General” tab > ”Properties button >
”Parameters” tab > ”Properties” button > ”Network Settings tab > ”Options
button
-- Activate equidistance on the DP master system
-- Set the length of the equidistant DP cycle (max. 32 ms).
-- Set ”Times Ti and To same for all Slaves” (results in synchronization of the
I/O data of the different DP slaves)
-- You can set the Ti and To times separately. Recommendation: Accept the
default settings for Ti and To.