Brief Instructions on Commissioning ET 200S
2-3
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Prerequisites
You must have set up an S7 station consisting of a power supply module and a
DP master (for example, CPU 315-2 DP). A CPU 315-2 DP was used as the
DP master in this example. However, any other DP master (IEC 61784-1:2002
Ed1 CP 3/1) could be used instead.
STEP 7 (V 5.0 with ServicePack 3 or higher) is fully installed on your
programming device (PG). You must be familiar with STEP 7.
The programming device must be connected to the DP master.
Installation
1. Mount the rail (35 mm x 7.5 mm or 15 mm) with a length of at least 210 mm on
a solid base.
2. Install the various modules on the rail beginning on the left (hook on, swing in,
move to the left). Adhere to the following sequence:
-- IM151-1 STANDARD interface module
-- TM-P15N23-A1 terminal module
-- 4 x TM-E15N24-A1 terminal modules
-- TM-P15N23-A1 terminal module
-- 4 x TM-E15N24-A1 terminal modules
-- Terminating module
3. Set the PROFIBUS address 3 on the IM 151-1 STANDARD interface module.
64
32
16
8
4
2
1
ONOFF
PROFIBUS address 3
Figure 2-2 Setting PROFIBUS Address 3