Analog Electronic Modules
12-12
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Measuring range for thermocouple type E
Table 12-16 SIMATIC S7 Format: Measuring Range Type E in °C and °F
Units
Units
Type E
in °C
decimal hexa
decimal
Type E
in °F
decimal hexa
decimal
Area
> 1200,0 32767 7FFF
H
> 2192,0 32767 7FFF
H
Overflow
1200,0
:
1000,1
12000
:
10001
2EE0
H
:
2711
H
2192,0
:
1832,1
21920
:
18321
55A0
H
:
4791
H
Overshoot range
1000,0
:
--270,0
10000
:
--2700
2710
H
:
F574
H
1832,0
:
--454,0
18320
:
--4540
4790
H
:
EE44
H
Nominal range
< --270,0 -- 32768 8000
H
< --454,0 -- 32768 8000
H
Underflow
Measuring range for thermocouple type J
Table 12-17 SIMATIC S7 Format: Measuring Range Type J in °C and °F
Units
Units
Type J
in °C
decimal hexa
decimal
Type J
in °F
decimal hexa
decimal
Area
> 1450,0 32767 7FFF
H
> 2642,0 32767 7FFF
H
Overflow
1450,0
:
1200,1
14500
:
12010
38A4
H
:
2EEA
H
2642,0
:
2192,1
26420
:
21921
6734
H
:
55A1
H
Overshoot range
1200,0
:
--210,0
12000
:
--2100
2EE0
H
:
F7CC
H
2192,0
:
--346,0
21920
:
--3460
55A0
H
:
F27C
H
Nominal range
< --210,0 -- 32768 8000
H
< --346,0 -- 32768 8000
H
Underflow