Terminal Module
9-13
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Terminal assignment
See the following table for the terminal assignment of the terminal module:
Table 9-6 Terminal assignment of the TM-P30S44-A0 and TM-P30C44-A0 terminal
module
View
Terminal Name
2 24 VDC 24 VDC load voltage for: inserted
power module, associated potential group.
DO 0 and DO 1 and P1 and P2 potential
rails
3 M Chassis ground
1
A4 AUX 1 Any terminal for PE or potential rail up to
the maximum rated load voltage of the
module
2
3
6
7
1
0
1
3
1
4
1
9
4
8
6 24 VDC 24 VDC load voltage for: inserted
power module, associated potential group.
DO 0 and DO 1 and P1 and P2 potential
rails
1
1
5
1
A
A
7 M Chassis ground
2
6
4
8
A8 AUX 1 Any terminal for PE or potential rail up to
the maximum rated load voltage of the
module
9 DO 0 P
Terminals for fail-safe digital output 0
10 DO 0 M
(P--M switching)
11 DO 2 P
Terminals (relay contacts) for fail-safe
switching of the P1 and P2 potential rails.
12 DO 2 M
an
can a
so
euse
as
and DO 2 P (for wiring diagram see
ET 200S Manual, Fail-safe Modules).
13 DO 1 P
Terminals for fail-safe digital output 0 (P --M
14 DO 1 M
switching)
15 DO 2 P
Terminals (relay contacts) for fail-safe
switching of the P1 and P2 potential rails.
16 DO 2M
an
can a
so
euse
as
and DO 2 P (for wiring diagram see
ET 200S Manual, Fail-safe Modules).
!
Caution
If high currents are encountered at DO 2 P and DO 2 M, terminals 11 and 15
(DO 2 P) and 12 and 16 (DO 2 M) must be wired in parallel.
Otherwise terminal overheating caused by the current load cannot be excluded.