Digital Electronic Modules
11-2
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
11.1 Parameters for digital electronic modules
Parameters for digital input modules
Table 11-1 Parameters for digital input modules
2DI
24 VDC
4DI
24 VDC
4DI
24--48 VUC
2DI/4DI 24 VDC
Standard
Value range Default
setting
Effective
range
High
Feature
High
Feature
High
Feature
4DI 2 4 VDC/SRC
Standard
g
g
2DI 120 VAC
Standard
2DI 230 VAC
Standard
Hardware interrupt
3)
-- -- -- -- -- --
disable
enabled
disable Module
-- -- -- Diagnostic
alarm
-- -- --
disable
enabled
disable Module
Input delay
1)
-- -- -- -- -- --
0.1 ms
0.5 ms
3ms
15 ms
3ms Module
Diagnosis: Short circuit as
per M
2)
-- -- -- -- -- --
disable
enabled
disable Module
-- -- -- Diagnosis:
wire break
4)
-- -- --
disable
enabled
disable Module
-- -- -- Diagnosis:
Fuse defect
-- -- --
disable
enabled
disable Module
-- -- -- Diagnosis:
no load
voltage
-- -- --
disable
enabled
disable Module
Trigger for
process
n
t
e
r
r
u
p
t
Trigger for
process
n
t
e
r
r
u
p
t
-- -- -- -- -- --
disable
enabled
disable
Channel 0
n
t
errup
t
,
rising
edge
3)
n
t
errup
t
,
rising
edge
3)
Channel 1
-- -- --
g
Channel 2
Channel 3
1)
The input delay applies to ”0” after ”1” and to ”1” after ”0”
2)
Short circuit of the sensor supply
3)
Configurable only with IM151-1 HIGH FEATURE and IM151-7 CPU interface module
4)
If the wire-break test is enabled, all free inputs must be stabilized so they do not trigger a module wire
break. This requires a resistor between terminal 24/48 V
(3, A4, 7, A8) and the free input. The resistor must supply an input current of at least 0.5 mA (see
”Sensor circuit in the technical specifications table). This ensures that sufficient current will flow to
prevent wire-break detection.
When switched off the sensor must supply at least 0.5 mA (otherwise a wire-break will be detected
when switched off). Alternatively a resistor can be installed parallel to the sensor terminals (current
must be at least 0.5 mA).