Commissioning and Diagnostics
6-44
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
1COUNT 24V/100kHz
Table 6-17 1Count 24V/100kHz
Error type
Meaning Remedy
1
D
00001: Short-circuit Short circuit of the sensor
supply or the actuator.
Check the wiring to the sensor.
Correct the process wiring.
5
D
00101: Overtemperature Digital output is overloaded. Correct the process wiring.
6
D
00110: Wire break Line to the actuator interrupted. Correct the process wiring.
9
D
01001: Error Internal module error occurred.
Load voltage from the power
module is too low.
Replace the module.
Correct the process wiring.
Check the load voltage.
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Adjust the parameter
assignment.
1COUNT 5V/500kHz
Table 6-18 1Count 5V/500kHz
Error type
Meaning Remedy
1
D
00001: Short-circuit Short circuit of the sensor
supply or the actuator.
Check the wiring to the sensor.
Correct the process wiring.
5
D
00101: Overtemperature Digital output is overloaded. Correct the process wiring.
6
D
00110: Wire break Line to the actuator interrupted. Correct the process wiring.
9
D
01001: Error Internal module error occurred. Replace the module.
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Adjust the parameter
assignment.
26
D
11010: External error/fault Wire break/short circuit of the 5
V sensor signals:
A,/A,B,/B,N,/N,
Correct the parameter settings
1STEP 5V/204kHz
Table 6-19 1STEP 5V/204kHz
Error type
Meaning Remedy
1
D
00001: Short-circuit Short circuit of the sensor
supply.
Check the wiring to the
switches. Correct the process
wiring.
9
D
01001: Error Internal module error occurred. Replace the module.
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Adjust the parameter
assignment.