EasyManua.ls Logo

Siemens SIMATIC ET 200S - Parameters for analog input modules U, I High Feature

Siemens SIMATIC ET 200S
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-30
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for
2AI U High Feature analog electronic module
2AI I 2/4WIRE High Feature analog electronic module
Table 12-31 Parameters for analog input modules U, I High Feature
2AI U High Feature
2AI I 2/4WIRE High
Feature
Value range Default setting Effective
range
Group diagnostics (configuration error,
internal error)
disable
enabled
disable Module
Diagnosis: underflow/overflow
disable
enabled
disable Module
-- -- -- Diagnosis: wire
break
1)
disable
enabled
disable Channel
Smoothing
No
weak
medium
strong
No Channel
Measurement type /
range
-- -- --
disabled
5V
1to5V
10 V
10 V Channel
-- -- -- Measurement type /
range
disabled
4to20mA
20 mA
4to20mA Channel
Interference Frequency Suppression
disable
enabled
disable Module
Run time calibration
disable
enabled
disable Module
1)
Only in 4 to 20 mA measurement range