Analog Electronic Modules
12-30
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Parameters for
• 2AI U High Feature analog electronic module
• 2AI I 2/4WIRE High Feature analog electronic module
Table 12-31 Parameters for analog input modules U, I High Feature
2AI U High Feature
2AI I 2/4WIRE High
Feature
Value range Default setting Effective
range
Group diagnostics (configuration error,
internal error)
•
disable
•
enabled
disable Module
Diagnosis: underflow/overflow
•
disable
•
enabled
disable Module
-- -- -- Diagnosis: wire
break
1)
•
disable
•
enabled
disable Channel
Smoothing
•
No
•
weak
•
medium
•
strong
No Channel
Measurement type /
range
-- -- --
•
disabled
•
5V
•
1to5V
•
10 V
10 V Channel
-- -- -- Measurement type /
range
•
disabled
•
4to20mA
•
20 mA
4to20mA Channel
Interference Frequency Suppression
•
disable
•
enabled
disable Module
Run time calibration
•
disable
•
enabled
disable Module
1)
Only in 4 to 20 mA measurement range