Siemens SIMATIC ET 200S - Block Diagram of the 2 AI I 2 WIRE Standard

Siemens SIMATIC ET 200S
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-56
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Block diagram
Backplane bus
ET 200S
backplane bus
interface
connection
ADC
M
ANA
24V
L+
1M
1
2
5
6
7
3
Current
limiting
P1
P2
MUX
Figure 12-10 Block diagram of the 2AI I 2WIRE Standard
Technical data
Dimensions and weight
Dimensions W x H x D
(mm)
15 x 81 x 52
Weight Approx. 40 g
Module-specific data
Supports clock synchro-
nized mode
No
Number of inputs 2
Cable length
shielded max. 200 m (164 ft)
Voltages, currents, electrical potentials
Rated load voltage L+ (from
power module)
24 VDC
Polarity reversal
protection
Yes
Transducer power supply Yes
Short-circuit protection Yes (destruction limit
35 mA per channel)
Electrical isolation
Between channels and
backplane bus
Yes
Between channels and
load voltage L+
No
Between the channels No
Isolation tested 500 VDC
Current consumption
with load voltage L+ max . 8 0 mA
Power loss of the module Typical 0.6 W
Status, interrupts, diagnostics
Diagnostic functions
Group error red LED ”SF”
Reading of diagnostics
functions
Yes