EasyManua.ls Logo

Siemens SIMATIC ET 200S - Module information

Siemens SIMATIC ET 200S
652 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and Diagnostics
6-36
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
6.1.6.7 Module information
Definition
The module status indicates the status of the configured modules and expands on
the module diagnosis as regards the configuration. The module status begins after
the module diagnosis and comprises:
7 bytes in the case of the IM151-1 BASIC
20 bytes in the case of the IM151-1 STANDARD, IM151-1 FO STANDARD and
IM151-1 HIGH FEATURE.
Module status
The module status for the ET 200S with the IM151-1 BASIC is structured as
follows:
Byte 9
Byte 10
70
Byte 11
70
82
H
0
H
0
H
76 54 132 0
Byte 13
Byte 12
Bit no.
Modules 1 to 4
Byte 14
Modules 5 to 8
Byte 15
Modules 9 to 12
00
B
: module OK; valid user data
01
B
: module error; invalid user data
10
B
: incorrect module; invalid user data
11
B
: no module (or module failure);
invalid user data
Status type: Module Status
irrelevant
irrelevant
70
Bit no.
Code for module status
00
56
Length of the module status
including byte 15 (= 7 bytes)
11
1
0
0
0
123
4
Figure 6-23 Structure of the module status for the ET 200S with the IM151-1 BASIC

Table of Contents