Analog Electronic Modules
12-29
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
12.4 Parameters for analog electronic modules
Parameters for
• 2AI U Standard analog electronic module
• 2AI I 2WIRE Standard electronic module
• 4AI I 2WIRE Standard electronic module
• 2AI I 4WIRE Standard electronic module
Table 12-30 Parameters for analog input modules U, I ST
2AI U
Standard
2AII2WIRE
Standard
4AII2WIREST
2AII4WIRE
Standard
Value range Default setting Effective
range
Group diagnostics (configuration error, internal error)
•
disable
•
enabled
disable Module
Diagnosis: underflow/overflow
•
disable
•
enabled
disable Module
Diagnosis:
wire break
2)
Diagnosis:
Wire break
Diagnosis:
Wire break
1)
•
disable
•
enabled
disable Channel
Smoothing
•
No
•
weak
•
medium
•
strong
No Channel
Measurement
type / range
-- -- -- -- -- --
•
disabled
•
¦
5V
•
1to5V
•
¦
10 V
10 V Channel
-- -- -- Measurement
type / range
-- -- --
•
disabled
•
2WIRE: 4 to
20mA
2WIRE: 4 to
20mA
Channel
-- -- -- -- -- -- Measurement
type / range
•
disabled
•
4WIRE: 4 to
20mA
•
4WIRE:
¦
20 mA
2WIRE: 4 to
20 mA
Channel
1)
Only in 4 to 20 mA measurement range
2)
Only in 1 to 5 V measurement range