Analog Electronic Modules
12-14
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Measuring range for thermocouple type N
Table 12-20 SIMATIC S7 Format: Measuring Range Type N in °C and °F
Units
Units
Type N
in °C
decimal hexa
decimal
Type N
in °F
decimal hexa
decimal
Area
> 1550,0 32767 7FFF
H
> 2822,0 32767 7FFF
H
Overflow
1550,0
:
1300,1
15500
:
13001
3C8C
H
:
32C9
H
2822,0
:
2372,1
28220
:
23721
6E3C
H
:
5CA9
H
Overshoot range
1300,0
:
--270,0
13000
:
--2700
32C8
H
:
F574
H
2372,0
:
--454,0
23720
:
--4540
5CA8
H
:
EE44
H
Nominal range
< --270,0 --32768 8000
H
--32768 8000
H
<EE44
H
Underflow
Measuring range for thermocouple type R, S
Table 12-21 SIMATIC S7 Format: Measuring Range Ty pe R, S in °C and °F
Units
Units
Type R, S
in °C
decimal hexa
decimal
Type R, S
in °F
decimal hexa
decimal
Area
> 2019,0 32767 7FFF
H
> 3276,6 32767 7FFF
H
Overflow
2019,0
:
1769,1
20190
:
17691
4EDE
H
:
451B
H
3276,6
:
3216,3
32766
:
32163
7FFE
H
:
7DA3
H
Overshoot range
1769,0
:
--50,0
17690
:
--500
451A
H
:
FE0C
H
3216,2
:
--58,0
32162
:
--580
7DA2
H
:
FDBC
H
Nominal range
--50,1
:
--170,0
--510
:
--1700
FE0B
H
:
F95C
H
--58,1
:
--274,0
--581
:
--2740
FDBB
H
:
F54C
H
Undershoot range
< --170,0 --32768 8000
H
< --274,0 --32768 8000
H
Underflow